For harmonic filtering. Line voltage 220 – 260 V.
Series: R
If you need more information you can contact us at sales@comlec.com
- Advantages of cast resin technique:
- Protection against corrosive environments
- Suitable for elevated vibration levels
- No damange of wire isolation due to current peaks
- Reduction of noise and internal vibrations
PRODUCTS IN THIS FAMILY
Reference | Description | In (A) | Motor rating | L (mH) | ||
---|---|---|---|---|---|---|
R2.5 | single phase cast resin line inductor | 2,5 A | 0,23 kW / 0,31 CV | 8,785 | ||
R4 | single phase cast resin line inductor | 4 A | 0,38 kW / 0,5 CV | 5,491 | ||
R5 | single phase cast resin line inductor | 5 A | 0,46 kW / 0,6 CV | 4,393 | ||
R6.3 | single phase cast resin line inductor | 6,3 A | 0,55 kW / 0,75 CV | 3,486 | ||
R8 | single phase cast resin line inductor | 8 A | 0,75 kW / 1 CV | 2,745 | ||
R10 | single phase cast resin line inductor | 10 A | 1,1 kW / 1,5 CV | 2,196 | ||
R12.5 | single phase cast resin line inductor | 12,5 A | 1,5 kW / 2 CV | 1,757 | ||
R16 | single phase cast resin line inductor | 16 A | 1,85 kW / 2,5 CV | 1,373 | ||
R20 | single phase cast resin line inductor | 20 A | 2,2 kW / 3 CV | 1,098 | ||
R25 | single phase cast resin line inductor | 25 A | 3 kW / 4 CV | 0,879 | ||
R31.5 | single phase cast resin line inductor | 31,5 A | 4 kW / 5,5 CV | 0,697 | ||
R40 | single phase cast resin line inductor | 40 A | 5,5 kW / 7,5 CV | 0,549 | ||
R50 | single phase cast resin line inductor | 50 A | 6,5 kW / 8,7 CV | 0,439 | ||
R63 | single phase cast resin line inductor | 63 A | 7,5 kW / 10 CV | 0,349 | ||
R80 | single phase cast resin line inductor | 80 A | 11 kW / 15 CV | 0,275 | ||
R100 | single phase cast resin line inductor | 100 A | 14 kW / 18,7 CV | 0,220 |
DIMENSIONS AND WEIGHTS
Reference | In (A) | Dimensions mm | Weight kg | Fig | ||||||
---|---|---|---|---|---|---|---|---|---|---|
A | B | C | D | E | Ø | |||||
R2.5 | 2,5 A | 50 | 97 | 84 | 80 | 34 | 6 | 0.76 | 1 | |
R4 | 4 A | 50 | 97 | 84 | 80 | 34 | 6 | 0.78 | 1 | |
R5 | 5 A | 50 | 97 | 94 | 80 | 34 | 6 | 0.94 | 1 | |
R6.3 | 6,3 A | 75 | 96 | 95 | 80 | 56 | 6 | 1.3 | 1 | |
R8 | 8 A | 75 | 96 | 95 | 80 | 56 | 6 | 1.3 | 1 | |
R10 | 10 A | 75 | 96 | 95 | 80 | 56 | 6 | 1.3 | 1 | |
R12.5 | 12,5 A | 75 | 96 | 95 | 80 | 56 | 6 | 1.3 | 1 | |
R16 | 16 A | 75 | 96 | 110 | 80 | 56 | 6 | 1.8 | 1 | |
R20 | 20 A | 84 | 102 | 120 | 86 | 65 | 6 | 2.7 | 1 | |
R25 | 25 A | 96 | 112 | 126 | 96 | 77 | 6 | 2.8 | 1 | |
R31.5 | 31,5 A | 96 | 112 | 126 | 96 | 77 | 6 | 2.9 | 1 | |
R40 | 40 A | 108 | 122 | 155 | 106 | 89 | 6 | 5 | 1 | |
R50 | 50 A | 126 | 145 | 167 | 125 | 102 | 6 | 5.6 | 2 | |
R63 | 63 A | 126 | 145 | 187 | 125 | 102 | 7 | 8.1 | 2 | |
R80 | 80 A | 126 | 145 | 187 | 125 | 102 | 7 | 8.3 | 2 | |
R100 | 100 A | 150 | 165 | 200 | 145 | 125 | 7 | 10.6 | 2 |
TECHNICAL CHARACTERISTICS
Isolation | Class B – 130º C |
Winding | Clase HC – 200ºC |
Cover | Cast resin |
Frequency | 50-60 Hz |
Protection degree | IP-20 |
Includes | Thermal protection against over temperature |
Standards | IEC/EN/UNE-EN 60076-6, CE |
Ambient temperature | 40ºC |
Line voltage | 220 – 260 V |
Test voltage | 3 kV (1 min, 50 Hz) |
- Voltage drop: 3%
- Reduction of current harmonics generated by the load, resulting in energy consumption reduction and power factor improvement
- Reduction of the crest factor of the current wave, extending the lifetime of the equipment and avoiding breakdowns
- Attenuation of microcuts in the supply voltage generated by power converters, causing malfuntioning of computers, PLC’s and other sensitive equipment
Copyright: Images and Specifications are property of POLYLUX, S.L
Please contact sales@comlec.com for assistance