RTF14X – THREE PHASE FILTERING INDUCTORS FOR CAPACITOR BANK, 14%

For protection of capacitors against harmonics. Line voltage 400 V at 50 Hz.
Series: RTF
filtering choke for capacitor bank, 14%
If you need more information you can contact us at sales@comlec.com
  • Inductances for capacitors protection
  • Low temperature rise

PRODUCTS IN THIS FAMILY

Reference Description Capacitor rating Effective rating Current
RTF14X5 filtering choke for capacitor bank 5 kVAr / 460V 4,3 kVAr 6,2 A
RTF14X10 filtering choke for capacitor bank 10 kVAr / 460V 8,6 kVAr 12,4 A
RTF14X12.5 filtering choke for capacitor bank 12,5 kVAr / 460V 10,8 kVAr 15,6 A
RTF14X15 filtering choke for capacitor bank 15 kVAr / 460V 12,9 kVAr 18,7 A
RTF14X20 filtering choke for capacitor bank 20 kVAr / 460V 17,2 kVAr 24,9 A
RTF14X25 filtering choke for capacitor bank 25 kVAr / 460V 21,6 kVAr 24,9 A
RTF14X30 filtering choke for capacitor bank 30 kVAr / 460V 25,9 kVAr 31,1 A
RTF14X40 filtering choke for capacitor bank 40 kVAr / 460V 34,5 kVAr 49,8 A
RTF14X50 filtering choke for capacitor bank 50 kVAr / 460V 43,1 kVAr 62,2 A
RTF14X60 filtering choke for capacitor bank 60 kVAr / 460V 51,7 kVAr 74,7 A
RTF14X80 filtering choke for capacitor bank 80 kVAr / 460V 69,0 kVAr 99,5 A
RTF14X100 filtering choke for capacitor bank 100 kVAr / 460V 86,2 kVAr 124,4 A

DIMENSIONS AND WEIGHTS

Reference Capacitor rating Dimensions mm Weight kg
A B C D E Ø
RTF14X5 5 kVAr / 460V 150 150 185 95 100 9 7.2
RTF14X10 10 kVAr / 460V 180 155 220 100 120 9 11.7
RTF14X12.5 12,5 kVAr / 460V 180 160 220 105 120 9 12.7
RTF14X15 15 kVAr / 460V 180 195 220 140 120 9 18.8
RTF14X20 20 kVAr / 460V 180 205 219 150 120 9 20.8
RTF14X25 25 kVAr / 460V 180 230 219 175 120 9 25.6
RTF14X30 30 kVAr / 460V 240 180 290 125 160 9 29.2
RTF14X40 40 kVAr / 460V 240 195 290 150 160 9 34.5
RTF14X50 50 kVAr / 460V 240 215 290 160 160 9 41.4
RTF14X60 60 kVAr / 460V 240 225 290 170 160 9 45.2
RTF14X80 80 kVAr / 460V 300 200 365 139 200 9 59
RTF14X100 100 kVAr / 460V 300 225 365 164 200 9 72

TECHNICAL CHARACTERISTICS

Isolation Class F – 155ºC
Windings Class HC – 200ºC
Harmonic currents I3 = 10 %, I5 = 9 %, I7 = 5 %
Thermal overload factor 5 %
Resonance frequency 134 Hz (P = 14 %)
Frequency 50 Hz
Protection degree IP-00
Includes Bimetal thermal protection agains over temperature
Temperature rise < 85 ºC
Standards IEC/EN/UNE-EN 60076-6 CE
Overcurrent In 6 %
Ambient temperature 45ºC
Capacitor voltage 460 V
Line voltage 400 V
Test voltage 3 kV (1 min, 50 Hz)
Inductance tolerance +/- 3 %
  • Avoids resonance between the inductance of the supply transformer and the capacity of the capactiro bank
  • Eliminates over voltage and over current in the transformer and the capacitor bank
  • Protects capacitors against harmonics, avoiding premature breakdown of the capacitor bank
  • Limits the connection spikes of the capacitor bank, extending its lifetime and reducing microcuts in the voltage

Copyright: Images and Specifications are property of POLYLUX, S.L
Please contact sales@comlec.com for assistance