With galvanic isolation.
Series: C
If you need more information you can contact us at sales@comlec.com
- Filtering of harmonics 5º, 7º, 11º, 13º, 17º, 19º
PRODUCTS IN THIS FAMILY
Reference | Description | Rating | Input voltage | Output voltage | ||
---|---|---|---|---|---|---|
C20F10 | C20F – Harmonic filter for industrial installations, with galvanic separation | 10 kVA | 400 V | 2 x 400 V+N | ||
C20F12.5 | C20F – Harmonic filter for industrial installations, with galvanic separation | 12,5 kVA | 400 V | 2 x 400 V+N | ||
C20F16 | C20F – Harmonic filter for industrial installations, with galvanic separation | 16 kVA | 400 V | 2 x 400 V+N | ||
C20F20 | C20F – Harmonic filter for industrial installations, with galvanic separation | 20 kVA | 400 V | 2 x 400 V+N | ||
C20F25 | C20F – Harmonic filter for industrial installations, with galvanic separation | 25 kVA | 400 V | 2 x 400 V+N | ||
C20F31.5 | C20F – Harmonic filter for industrial installations, with galvanic separation | 31,5 kVA | 400 V | 2 x 400 V+N | ||
C20F40 | C20F – Harmonic filter for industrial installations, with galvanic separation | 40 kVA | 400 V | 2 x 400 V+N | ||
C20F50 | C20F – Harmonic filter for industrial installations, with galvanic separation | 50 kVA | 400 V | 2 x 400 V+N | ||
C20F63 | C20F – Harmonic filter for industrial installations, with galvanic separation | 63 kVA | 400 V | 2 x 400 V+N | ||
C20F80 | C20F – Harmonic filter for industrial installations, with galvanic separation | 80 kVA | 400 V | 2 x 400 V+N | ||
C20F100 | C20F – Harmonic filter for industrial installations, with galvanic separation | 100 kVA | 400 V | 2 x 400 V+N | ||
C20F125 | C20F – Harmonic filter for industrial installations, with galvanic separation | 125 kVA | 400 V | 2 x 400 V+N | ||
C20F160 | C20F – Harmonic filter for industrial installations, with galvanic separation | 160 VA | 400 V | 2 x 400 V+N | ||
C20F200 | C20F – Harmonic filter for industrial installations, with galvanic separation | 200 kVA | 400 V | 2 x 400 V+N | ||
C20F250 | C20F – Harmonic filter for industrial installations, with galvanic separation | 250 kVA | 400 V | 2 x 400 V+N |
DIMENSIONS AND WEIGHTS
Reference | Rating | Dimensions mm | Weight kg | Fig | ||||||
---|---|---|---|---|---|---|---|---|---|---|
A | B | C | D | E | Ø | |||||
C20F10 | 10 kVA | 595 | 415 | 708 | 375 | 350 | 12 | 103 | ||
C20F12.5 | 12,5 kVA | 595 | 415 | 708 | 375 | 350 | 12 | 109 | ||
C20F16 | 16 kVA | 595 | 415 | 708 | 375 | 350 | 12 | 131 | ||
C20F20 | 20 kVA | 595 | 415 | 708 | 375 | 350 | 12 | 153 | ||
C20F25 | 25 kVA | 595 | 415 | 708 | 375 | 350 | 12 | 173 | ||
C20F31.5 | 31,5 kVA | 789 | 490 | 965 | 450 | 415 | 13 | 213 | ||
C20F40 | 40 kVA | 789 | 490 | 965 | 450 | 415 | 13 | 253 | ||
C20F50 | 50 kVA | 789 | 490 | 965 | 450 | 415 | 13 | 289 | ||
C20F63 | 63 kVA | 985 | 575 | 1310 | 475 | 470 | 18 | 405 | ||
C20F80 | 80 kVA | 985 | 575 | 1310 | 475 | 470 | 18 | 449 | ||
C20F100 | 100 kVA | 985 | 575 | 1310 | 475 | 470 | 18 | 497 | ||
C20F125 | 125 kVA | 985 | 575 | 1310 | 475 | 470 | 18 | 607 | ||
C20F160 | 160 VA | 1195 | 635 | 1620 | 535 | 690 | 18 | 758 | ||
C20F200 | 200 kVA | 1195 | 635 | 1620 | 535 | 690 | 18 | 830 | ||
C20F250 | 250 kVA | 1195 | 635 | 1620 | 535 | 690 | 18 | 1136 |
TECHNICAL CHARACTERISTICS
Isolation | Class H – 180ºC |
Winding | Class HC – 200ºC |
Cover | In metal enclosure, epoxy polyester painted |
Filtering of harmonics coming from the load | 5, 7, 17, 19 5, 7, 11, 13, 17, 19 in combination with RTL o RTLX inductances |
Frequency | 50-60 Hz |
Protection degree | IP-23 |
Includes | Lifting eyebolts as from 31,5 kVA |
Set of wheels (optional) | RUE060 wheels from C20F10 to C20F50 RUE125 wheels from C20F63 to C20F250 |
Standards | IEC/EN/UNE-EN 60076 – 60726, CE IEC/EN/UNE-EN 61000-3-2, CE IEC/EN/UNE-EN 61000-3-4 IEE 519, CE |
Reduction of phase current up to | 20 % 35 % in combination with RTL o RTLX inductances |
Reduction of THD-I y THD-V up to | 60 % 85 % in combination with RTL o RTLX inductances |
Cooling | ANAN |
Ambient temperature | 30ºC |
Test voltage | 3 kV (1 min, 50 Hz) |
- Input voltage: 400V, output: 2 x 400V + N
- Note: For selection, please consult the application guide