Series: C
If you need more information you can contact us at sales@comlec.com
- Filtering of harmonics 5th, 7th, 11th, 13th, 17th, 19th
PRODUCTS IN THIS FAMILY
Reference | Description | Rating | Input voltage | Output voltage | ||
---|---|---|---|---|---|---|
C10F10 | C10F – Harmonic filter for industrial installations | 10 kVA | 400 V + N | 400 V + N | ||
C10F12.5 | C10F – Harmonic filter for industrial installations | 12,5 kVA | 400 V + N | 400 V + N | ||
C10F16 | C10F – Harmonic filter for industrial installations | 16 kVA | 400 V + N | 400 V + N | ||
C10F20 | C10F – Harmonic filter for industrial installations | 20 kVA | 400 V + N | 400 V + N | ||
C10F25 | C10F – Harmonic filter for industrial installations | 25 kVA | 400 V + N | 400 V + N | ||
C10F31.5 | C10F – Harmonic filter for industrial installations | 31,5 kVA | 400 V + N | 400 V + N | ||
C10F40 | C10F – Harmonic filter for industrial installations | 40 kVA | 400 V + N | 400 V + N | ||
C10F50 | C10F – Harmonic filter for industrial installations | 50 kVA | 400 V + N | 400 V + N | ||
C10F63 | C10F – Harmonic filter for industrial installations | 63 kVA | 400 V + N | 400 V + N | ||
C10F80 | C10F – Harmonic filter for industrial installations | 80 kVA | 400 V + N | 400 V + N | ||
C10F100 | C10F – Harmonic filter for industrial installations | 100 kVA | 400 V + N | 400 V + N | ||
C10F125 | C10F – Harmonic filter for industrial installations | 125 kVA | 400 V + N | 400 V + N | ||
C10F160 | C10F – Harmonic filter for industrial installations | 160 kVA | 400 V + N | 400 V + N | ||
C10F200 | C10F – Harmonic filter for industrial installations | 200 kVA | 400 V + N | 400 V + N |
DIMENSIONS AND WEIGHTS
Reference | Rating | Dimensions mm | Weight kg | Fig | ||||||
---|---|---|---|---|---|---|---|---|---|---|
A | B | C | D | E | Ø | |||||
C10F10 | 10 kVA | 525 | 415 | 640 | 375 | 350 | 12 | 80 | ||
C10F12.5 | 12,5 kVA | 525 | 415 | 640 | 375 | 350 | 12 | 96 | ||
C10F16 | 16 kVA | 595 | 415 | 708 | 375 | 350 | 12 | 101 | ||
C10F20 | 20 kVA | 595 | 415 | 708 | 375 | 350 | 12 | 109 | ||
C10F25 | 25 kVA | 595 | 415 | 708 | 375 | 350 | 12 | 128 | ||
C10F31.5 | 31,5 kVA | 595 | 415 | 708 | 375 | 350 | 12 | 153 | ||
C10F40 | 40 kVA | 789 | 490 | 965 | 450 | 415 | 13 | 197 | ||
C10F50 | 50 kVA | 789 | 490 | 965 | 450 | 415 | 13 | 213 | ||
C10F63 | 63 kVA | 789 | 490 | 965 | 450 | 415 | 13 | 248 | ||
C10F80 | 80 kVA | 789 | 490 | 965 | 450 | 415 | 13 | 290 | ||
C10F100 | 100 kVA | 985 | 575 | 1310 | 475 | 470 | 18 | 398 | ||
C10F125 | 125 kVA | 985 | 575 | 1310 | 475 | 470 | 18 | 448 | ||
C10F160 | 160 kVA | 985 | 575 | 1310 | 475 | 470 | 18 | 517 | ||
C10F200 | 200 kVA | 985 | 575 | 1310 | 475 | 470 | 18 | 625 |
TECHNICAL CHARACTERISTICS
Isolation | Class H – 180ºC |
Winding | Class HC – 200ºC |
Cover | In metal enclosure, epoxy polyester painted |
Filtering of harmonics coming from the load | 5, 7, 17, 19 5, 7, 11, 13, 17, 19 in combination with RTL or RTLX inductances |
Frequency | 50-60 Hz |
Protection degree | IP-23 |
Includes | Lifting eyebolts as from 40 kVA |
Set of wheels (optional) | RUE060 wheels from C10F16 to C10F80 RUE125 wheels from C10F125 to C10F200 |
Standards | IEC/EN/UNE-EN 60076 – 60726, CE IEC/EN/UNE-EN 61000-3-2, CE IEC/EN/UNE-EN 61000-3-4 IEE 519, CE |
Reduction of phase current up to | 20 % 35 % in combination with RTL or RTLX inductances |
Reduction of THD-I and THD-V up to | 60 % 85 % in combination with RTL or RTLX inductances |
Cooling | ANAN |
Ambient temperature | 30ºC |
Test voltage | 3 kV (1 min, 50 Hz) |
- Input voltage: 400 V+N, output: 400 V+N
- Note: For selection, please consult the application guide